BPIT, Inc. - Gas Fired Igniters Tube Ø48.3 mm

Gas Fired Igniters Tube Ø48.3 mm

By: Durag


Ignition of main burners in furnaces, boilers, power plants and incinerators.


BPIT, Inc. - Quotation icon Get a quote »



Features:

  • High energy ignition, Insensitive to moisture
  • Material burner tube stainless steel 310
  • Material connection enclosure stainless steel 316
  • Self-aspirating, forced air supply or combination
  • For self-aspirating version no air supply line required
  • Insensitive to pressure fluctuations (draft and windbox)
  • Integrated spark plug and ionisation electrode
  • Min. and max. temperature for connection enclosure: -40 to 80 °C, IP66
  • Electrical connection, 2 x M20x1,5 mm cable gland
  • Connection to main burner: 2" Ansi 150 LBS RF - Gas connection: ½" NPTF
  • Gas nozzle can be cleaned without disconnection of the process connections

Specifications:

Self-aspirating ignition burner      
Type: L48AV18JB-L-A-V
(Large nozzle, 1,9 mm for natural gas)
48AV13JB-L-A-VE 48AV13JB-L-A-V2E
Heat release with natural gas: 20–38 kW 46–75 kW 80–132 kW
Heat release with propane: 22-40 kW 67-109 kW 120-195 kW
Min. max pressure: 0,2 - 0,8 Barg
0,5 - 0,8 Barg for refinery gas (H2 > 30 vol%)
0,5 - 1,5 Barg 0,5 - 1,5 Barg
Length L: From 400 to 3000 mm From 400 to 3000 mm     From 400 to 3000 mm
Air inlet A: 175 mm
> 300 mm
> 300 mm > 300 mm
Air conn. for forced draft: 1/2" NPTF 1/2" NPTF 1/2" NPTF
Ignition: High energy
one sparkplug
High energy
one sparkplug
High energy
one sparkplug
Flame detection: Ionisation Ionisation Ionisation
       
Self-aspirating ignition burner      
Type: 48AV13JB-L-A-V4E    
Heat release with natural gas: 150-250 kW    
Heat release with propane: 226-370 kW    
Min. max. pressure: 0,5 - 1,5 Barg    
Length L: From 400 to 3000 mm    
Air inlet A: > 300 mm    
Air conn. for forced draft: 1/2" NPTF    
Ignition: High energy one sparkplug    
Flame detection: Ionisation